PyroGuard Engineering

Secondary Filter Application

Secondary Filter Application

 Sensor to Valve Distance (SVD) =

 SU-1 and SU-2 Suppression Units: Velocity (feet per minute) divided by 60 multiplied by .3

 SU-3 Suppression Units: Velocity (feet per minute) divided by 60 multiplied by .4

 Sensor to Abort Gate Distance (SAGD) =

 4"- 43" diameter:  Velocity (feet per minute) divided by 60 multiplied by .5

 44" diameter:  Velocity (feet per minute) divided by 60 multiplied by .6

 Water Requirments:

 Water volumes and pressures vary for each suppression assembly.  This requirement is carfully engineered from reliable information provided by the customer. Field data sheet accuracy is critical.

 Sensor Location Guidelines:

 To reduce lens wear it is recommended that sensors (S-1) be installed with a minimum of three (3) pipe diameters of straight duct prior to their location.  This will also allow sparks generated in high abrasion areas to extinguish themselves, therefore minimizing the number of alarms.

 Recommended location of second set of sensors (S-2) to be one (1) 'SVD" beyond the suppression unit.

 Suppression Unit Location Guidelines:

 Nozzles to be located to allow for a minimum of three (3) pipe diameters between nozzles and collector/filter inlet.

Secondary Filter Application

Secondary Filter Application

Primary Filter Application

Primary Filter Application
Primary Filter Application

Notes:

1. We have shown just a few of the many varied applications.  Please CONTACT US for design of the specific system to fit your needs.

2. Equipment shown provides optimum protection, however, Clarke's can custom design a system to fit your specific budget requirements.

Would you like Clarke's PyroGuard to determine what type of spark detection equipment  you need for your system or give you a quote on a system?  Download our Field Data Sheet by selecting the download button below, fill it out and fax it back to Clarke's PyroGuard at 541-345-1447. Please fill out one Field Data Sheet for each Zone of protection you require.  A Clarke's Sales Engineer will be in contact with you as soon as possible.  Thank you. 

Download Field Data Sheet

The Clarke's PyroGuard Field Data Sheet is in Adobe Acrobat Format.  If you need the Acrobat Reader please select the link below to go to the Adobe Acrobat Reader download page.

Get Acrobat Reader

 [Clarke's Sheet Metal] [Clarke's Allied] [Fire Management] [Clarke's South America] [China] [Canada]

 [Consoles] [Extinguishment] [Sensors] [Abort Gates] [Booster Pumps] [Other Detectors] [Test Lights]

 [Interface Device] [Software] [PyroComm] [OmniServer] [Engineering] [Get A Quote] [TroubleShooting]

[Contact Us] [Trade Shows] [About PyroGuard] [Spare Parts] [Related Links] [Whats New] [Home]

Made In America

COPYRIGHT 2000, Clarke's Sheet Metal, Inc, ALL RIGHTS RESERVED.